AMMP Edge installation and acceptance test

Last updated · View as markdown

AMMP Edge is AMMP's on-site datalogger. It reads equipment that has no cloud API, such as generator controllers, fuel sensors, meters and irradiance sensors, and sends the data to AMMP. It runs on a Strato Pi or UniPi device.

This guide is for installers. Start with the router and datalogger setup. For connecting specific equipment, such as generator controllers, fuel sensors, meters or irradiance sensors, contact support@ammp.io for the current wiring and configuration guidance.

Required materials

  • A laptop
  • A Strato Pi or UniPi server device
  • AC power supply
  • MicroSD card, 8 GB or larger
  • Wired Ethernet connection with internet access, for example a router
  • 24 V DC power supply
  • Digital multimeter
  • 1.5 mm² 4-core shielded flexible cable
  • LAN tester

Installation

  1. Check that you have all the materials above.
  2. Download the AMMP Edge SD card image:
  3. Write the image to the MicroSD card with balenaEtcher (Windows, macOS or Linux).
  4. Insert the card into the datalogger's SD card slot. If in doubt, see the Strato Pi user guide or the UniPi knowledge base.
  5. Install the datalogger and router. See Router and datalogger setup.
  6. Connect any generators, sensors or meters. Contact support@ammp.io for the wiring and configuration of your specific equipment.

Acceptance test

  1. Request the AMMP acceptance test (AT) document from support@ammp.io.
  2. Open the datalogger interface at http://192.168.4.1:8000/. It shows the Node ID and basic diagnostics, such as online status.
  3. Run a full site scan and let the datalogger generate its configuration automatically.
  4. Confirm the configuration.
  5. Run any custom actions needed, for example changing a sensor's Modbus address. AMMP support can tell you which ones apply to your equipment.
  6. Check that the real-time readings match what you see on site.
  7. Fill in the AT document with all the requested information and the scan results.
  8. Send the completed AT report to AMMP.

Note

Every device installed on site should appear in the full scan. If one is missing, check its wiring and address before completing the AT.